2.8 Operational faults
No display on the controller:
Is the heating plant's main switch turned on?
Are the fuses in order?
Check the wiring
Heating control does not function. There is no display of the time of day, or the
time displayed is incorrect
Check fuses of the plant
Make a reset: Isolate controller from the mains supply for about 5 seconds (e.g. turn
off the boiler's main switch for 5 seconds)
Set the correct time of day on the controller (operating line 1)
Check the time of day on the clock time master if the controller is used in a system
Controlling element does not open / close or does not operate correctly.
Manual lever of controlling element may not be engaged
Wiring to the controlling element interrupted (output test)
Check wiring of the sensors (input test)
Quick setback or the automatic 24-hour heating limit is active
Check the settings
Heating circuit pump does not run
Is the right type of plant displayed (setting line 53)?
Check wiring and fuse (output test)
Check wiring of the sensors (input test)
Check the settings
Burner does not switch on
Press burner's reset button
Check the fuses
Wiring to the controlling element interrupted (output test)
Check the electromechanical control thermostat (TR) and the manual reset safety
limit thermostat (STB)
Quick setback or automatic 24-hour heating limit is active
Check wiring of the boiler temperature sensor (input test)
Pump does not run
Check wiring and fuse (output test)
Check wiring of the sensors (input test)
D.h.w. is not being heated
Has the button for d.h.w. heating been activated?
Check setting of the electromechanical control thermostat (TR) installed on the
boiler. It must be above the TKmax setting
Check setpoint of the d.h.w. temperature
Check actual value of the d.h.w. temperature
Check if d.h.w. heating is released