EasyManua.ls Logo

Siemens RVA53.242 - Page 122

Siemens RVA53.242
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
122/218
Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of heating engineer settings 26.03.2001
4.56.3 Temperature-time integral
This temperature-time integral generates the locking signal for restricting the heating
circuits.
Diagram Procedure
a to b Within a foreseeable period of time, the actual boiler temperature (TKx)
will not lie within half the switching differential of the boiler temperature
setpoint.
è Locking signal will be built up
b to c,
d to e
Within a foreseeable period of time, the actual boiler temperature (TKx)
will lie within half the switching differential of the boiler temperature
setpoint.
è Locking signal will remain at a constant level
c to d,
e to f
Within a foreseeable period of time, the actual boiler temperature (TKx)
will lie above TKw.
è Locking signal will be decreased
f The actual boiler temperature (TKx) exceeds the boiler temperature
setpoint.
è Locking signal will be set to 0 %.
TKx
2378Z11
t
a
b
TK
TKw
0% t
y
x%
c
d
e
f
SDK/2
a Start of d.h.w. heating
TK boiler temperature
TKw Boiler temperature setpoint
TKx Actual value of the boiler temperature
SDK Switching differential of the boiler
t Time
Y Locking signal
Diagram

Table of Contents

Related product manuals