Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Handling 26.03.2001
RVA63.242
RVA53.242
Function
Range
Unit
Resolution
Factory
setting
98 - Solar application
0 No solar
1 Solar in d.h.w. storage tank
2 Solar in buffer storage tank
0...2 - 1 0
99 - Sensor input B8/B6
0 Flue gas Pt 1000
1 Collector Ni 1000
2 Collector Pt 1000
0...2 - 1 0
Heating circuit
100 100 Parallel displacement of
heating circuits 1 and 2
-4.5...+4.5 °C (K) 0.5 0.0
101 101 Room influence
0 Inactive
1 Active
0 / 1 - 1 1
102 102 Switching differential of room temperature (SDR)
heating circuits 1 and 2
- - . - Inactive
0.5...4.0 Active
- -:-...4.0 °C (K) 0.5 - -:-
103 103 Operating mode of room unit
0 Acting on heating circuit 1
1 Acting on heating circuit 2
2 Acting on heating circuits 1 and 2
0...2 - 1 0
104 104 Room unit values
0 Acting on heating circuit 1
1 Acting on heating circuit 2
2 Acting on heating circuits 1 and 2
0...2 - 1 0
105 105 Min. limitation of flow temperature setpoint
(TVmin) heating circuit 1
TVmax Line 107
8...TVmax °C 1 8
106 106 Min. limitation of flow temperature setpoint
(TVmin) heating circuit 2
TVmax Line 108
8...TVmax °C 1 8
107 107 Max. limitation of flow temperature setpoint
(TVmax) heating circuit 1
Tvmin Line 105
TVmin...95 °C 1 80
108 108 Max. limitation of flow temperature setpoint
(TVmax) heating circuit 2
Tvmin Line 106
TVmin...95 °C 1 80
109 109 Max. forward shift of optimum start control
0 No forward shift
00:00...06:00 hh:mm 10 min 00:00
110 110 Max. forward shift of optimum start control
0 No forward shift
00:00...06:00 hh:mm 10 min 00:00
113 113 Type of building construction
0 Heavy
1 Light
0 / 1 - 1 1
114 114 Adaption of heating curve HK1+HK2
0 Inactive
1 Active
0 / 1 - 1 1
115 115 Gain of locking signal 0...200 % 1 100
116 - Floor curing HK1
0 Off
1 Functional heating
2 Floor curing heating
3 Functional and floor curing heating
0...3 - 1 0
D.h.w.