Document Number 129-410 RWD62U Controller Installation and Commissioning Guide
October 1, 2004
Page 2 of 10 Siemens Building Technologies, Inc
Table 1. Application Numbers.
Main Loop
H = Heating
C = Cooling
(First digit =
Main control loop
Second digit = Auxiliary
control loop)
SP
SP
SP
SP
SP
SP
Auxiliary Loop
#1 ×
H Sequence
#2 ×
H + H
Sequences
# 3 ×
H + C Sequences
#4 ×
C Sequence
#5 ×
C + C
Sequences
#x0 (No auxiliary) #10 #20 #30 #40 #50
#x1 (Remote setpoint) #11 #21 #31 #41 #51
#x2 (Absolute limiter) #12 #22 #32 #42 #52
#x3 (Relative limiter) #13 #23 #33 #43 #53
#x4 (Comp. shift) #14 #24 #34 #44 #54
#x5 (Cascade) #15 #25 #35 #45 #55
#x6 (Win/Sum Digital) #16 #26 #36 – –
#x7 (Win/Sum Analog) #17 #27 #37 – –
#x8 (Maximum priority) – – #38 #48 #58
#x9 Main loop (Active input) #19 #29 #39 #49 #59
NOTES:
1. Application sheets for the listed applications are available online.
2. The heating sequence output is set to Direct Acting (default). This is typically used for normally open
valves. Output can be set to reverse acting by changing the MIN and MAX value. See PS4.
3. The cooling sequence output is set to Direct Acting (default). This is typically used for normally closed
valves. Output can be set to reverse acting by changing the MIN and MAX value. See PS4.