Document Number 129-410 RWD62U Controller Installation and Commissioning Guide
October 1, 2004
Page 6 of 10 Siemens Building Technologies, Inc
Main Display
Y1
Y2
X2
5.0
72°F
The main display shows:
Y1 and Y2 outputs in Volts dc. (0 to 10V will be display as 0, 1, 2 through 10)
Whether day or night setpoint is selected ( = day, e
= night).
X1 value in °C, °F, % or no unit.
Other displays are available by pressing the + button. The various displays are listed
below in sequence from the main display.
On entering any of the setpoint displays, the setpoint on display can be adjusted by
pushing the SEL
button. Increase value by pressing the + button, or decrease the
value by pressing the button. When the required value is reached, press the SEL
button to save the new value.
Alternative displays return to the main display after 20 seconds.
Table 3. Main Display.
Action
Typical Display
Selected Display Comments
Push ---
Y1 Y2 X1
Default page includes:
X1 reading,
Y output status
Day/night setpoint selection status
Push + button
Y1 SP – h
66.0°F (19.0°C)
Setpoint page, setting value displayed and is
adjustable:
First stage heating or cooling, direct or reverse day
acting setpoint, depending on application.
Push + button
Y2 SP – c
70.0°F (21.0°C)
Setpoint page, setting value displayed and is
adjustable:
Second stage heating or cooling, direct or reverse day
acting setpoint, depending on application.
Push + button
Y1 SP – h e
59.0°F (15.0°C)
Setpoint page, setting value displayed and is
adjustable:
First stage heating or cooling, direct or reverse night
acting setpoint, depending on application
Push + button
Y2 SP – c e
77.0°F (25.0°C)
Setpoint page, setting value displayed and is
adjustable:
Second stage heating or cooling, direct or reverse night
acting setpoint, depending on application
Push + button
X1
68.0°F (20.0°C)
X1 – Main sensor reading
Push + button
X2
50.0°F (10.0°C)
X2 – Auxiliary sensor reading.
Push + button
Y1 5.0
Output page: output value displayed
First stage Y1 value in Vdc
Push + button
Y2 0.0
Output page: output value displayed
Second stage Y2 value in Vdc
Push + button
#33
Application number and control sequence diagram
After 20 seconds any
page will return to the
main default page if
left unattended.
Y1 Y2 X1 Back to main default page