RWD62U Controller Installation and Commissioning Guide Document Number 129-410
October 1, 2004
Siemens Building Technologies, Inc. Page 7 of 10
Service (PS) Mode
Screen Sequence
Press both buttons + and and hold for five seconds to enter the Service
Mode.
Press + for viewing the next page or to increase value.
Press for viewing the previous page or to decrease value.
Press to enter the PS page or edit and save the value when the page
appears with the logo.
On entering service (PS) mode, PS4 appears first.
For initial setup, proceed directly to PS1 and enter your desired application
number first.
PS1 will already be opened if power has never been connected to the new
controller. See Figure 1.
PS2 to PS4 parameters may need to be adjusted for service/commissioning
purposes.
Commissioning
Flowchart
RWD0428R1
- Max/Min limiter
- Proportion band
- Integral time
- Compensation shifts start/end point
- Winter/Summer changeover temp.
and time delay
Auxiliary loop
- Day/night setpoint
- Winter/summer setpoint
- Define the unit as
o
F,
o
C, %
or no unit
- Sensor type
- Sensing range
- Calibration offset
Define unit, X1 & X2
- Application no. selection
Application no.
- Proportion band
- Integral time
- Output for minimum end
- Output for maximum end
- Day/night setpoint
- Winter/summer setpoint
Main loop
X1Y1 Y2
(wait 2 seconds)
New controller application
and setpoint sequence
* New controller
Normal programming
74°F00
Figure 1. Commissioning Flowchart.