12-4 Siemens PM240-2_EN_rev00-30082019.docx
permissible value
Line supply infeed failed or
interrupted
Line phase interrupted
Check the line supply phases.
Check the line supply voltage
setting (p0210)
F30015
Power unit: Phase failure motor cable
A phase failure in the motor feeder
cable was detected
The motor is correctly connected,
however the closed-speed control
is instable and therefore an
oscillating torque is
generated
Check the motor feeder cables
Check the speed controller
settings
A30016
Power unit: Load supply switched out
The DC link voltage is too low
Switch on load supply
Check the line supply if
necessary.