EasyManua.ls Logo

Siemens S7-1200 - Page 87

Siemens S7-1200
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration and operation
4.15 STEP 7 configuration of individual parameters
CP 1243-7 LTE
Operating Instructions, 01/2015, C79000-G8976-C381-01
87
Requirements and necessary information
Remember the following requirements in the CP configuration for the transfer of messages:
Enabling telecontrol communication ("Communication types") parameter group
Activating security functions
Additionally for e-mails: Configuring the "E-mail configuration" parameter group
To do this, you require the following information:
Access data of the SMTP server: Address, port number, user name, password
When using STARTTLS or SSL/TLS: Certificate of the e-mail service provider
Email address of the recipient
Text of the message optionally with the value of a PLC tag
In the text of every message, you can not only transfer the configured text but also the value
of a PLC tag. To do this enter "$$" as a placeholder for the value to be sent in the message
text. For the configuration, refer to the next section "Include value".
Enable status identifier / External status
If this option is enabled in STEP 7, a status is output on the CP that provides information
about the processing status of the sent message. The status is written to a PLC tag of the
type DWORD that is specified in the "External status" box.
The meaning of the statuses is as follows:
Table 4- 4 SMS: Meaning of the status ID output in hexadecimal format
Status
Meaning
0000
Transfer completed free of errors
8001 Error in the transfer, possible causes:
SIM card invalid
No network
Wrong destination phone number (number not reachable)

Table of Contents