Performance data
2.3 SEND/RECEIVE interface
CP 443-1 Advanced
Equipment Manual, 03/2023, C79000-G8976-C256-07
23
Characteristic
Explanation / values
Maximum data length for AG_SEND and
AG_RECV program blocks
AG_SEND and AG_RECV were shipped with predecessors of the CP and
allow the transfer of user data with a length from 1 to 240 bytes. The
version of the CP described here continues to support these blocks.
Maximum data length for AG_LSEND and
AG_LRECV program blocks
AG_LSEND and AG_LRECV allow the transfer of user data with the
following lengths:
1. ISO-on-TCP, TCP, ISO transport: 1 to 8192 bytes
2. UDP: 1 to 2048 bytes
3. E-mail (job header + user data): 1 to 8192 bytes
Maximum data length for
AG_SSEND and AG_SRECV program blocks
AG_SSEND and AG_SRECV allow the transfer of user data with the
following lengths:
1. ISO-on-TCP, TCP, ISO transport: 1 to 1452 bytes
2. UDP: 1 to 1452 bytes
LAN interface max. data field length generated
by CP per protocol data unit
sending
ISO transport, ISOonTCP, TCP:
400 bytes / TPDU with AG_SEND / AG_LSEND
1452 bytes / TPDU with AG_SSEND
receiving
ISO transport: 512 bytes / TPDU
ISO-on-TCP: 1452 bytes / TPDU
TCP: 1452 bytes / TPDU
* Notes on TCP connections:
Avoid receive overload
The flow control on TCP connections cannot control permanent overload of the recipient.
You should therefore make sure that the processing capabilities of a receiving CP are not
continuously exceeded by the sender (approximately 150200 messages per second).
TCP connections for FTP
Of the available TCP connections, a maximum of 20 TCP connections can be configured /
used with the "Use FTP protocol" option; see Characteristic data for FTP / FTPS mode
(Page 27).
Restrictions for UDP
Transfer is not confirmed
The transmission of UDP frames is unconfirmed, in other words the loss of messages is not
detected or displayed by the send blocks (AG_SEND or AG_LSEND).
No receipt of UDP broadcast
To avoid overload due to high broadcast load, the CP does not allow reception of UDP
broadcasts.
As an alternative, use the multicast function over a UDP connection. This allows you to
register the CP as a node in a multicast group.