Requirements for use
3.3 Project engineering
CP 443-1 Advanced
34 Equipment Manual, 03/2023, C79000-G8976-C256-07
CPU Article number of
the CPU: 6ES7...
As of CPU
firmware
version
a = multiprocessor mode
b = number of operable CPs
c = CPU resources for SEND/RECEIVE jobs
1
)
d = LOCK/UNLOCK
4)
3) 5)
2)
3) 6)
2)
3)
2)
3)
2)
Legend:
+ → The feature is supported / the specified mode is possible.
- → The feature is not supported / the specified mode is not possible.
1) The calculation of the maximum number of SEND/RECEIVE calls that can be used simultaneously per CP is described in
the section "Characteristic data".
2) When operating the CP as a PROFINET IO controller, the multiprocessor mode is not supported, i.e. only the process
image of the assigned CPU can be distributed via the CP (note: this has no influence on communications protocols
operating at the same time in multiprocessor mode).
3) When operating with H-CPUs with a firmware version lower than V6.0, the SSEND / SRECV mode on the SEND/RECV
interface is not supported.
4) The PROFINET IO mode Shared Device requires a CPU as of V5.3.
5) Only for use with PCS 7
6) Only for use with PCS neo
For the maximum possible number of SEND/RECEIVE calls for the CP, refer to the section
Number of simultaneous SEND/RECEIVE calls (Page 24).
3.3 Project engineering
Configuration and downloading the configuration data
It is possible to download the configuration data to the CP via MPI or LAN/Industrial Ethernet.
Downloading is possible over the PROFINET or the gigabit interface of the CP. You require
STEP 7 with additional modules in the following version:
Table 3- 1 Lowest required STEP 7 version
Either STEP 7 V5 or STEP 7 Professional
CP 443-1 Advanced functionality
• STEP 7 V5.6
• Security Configuration Tool (SCT) V4.1 ***
SCT is used in the configuration of the security function from
within STEP 7.
• Program block library "SIMATIC NET CP" version V5.5.4 **
The functionality of firmware version V3.1.x
can be used.