Upkeep and maintenance
6.1 Device configuration with PRESET-PLUG
SCALANCE W788-x / W748-1
Operating Instructions, 09/2017, A5E03678333-12
51
Note
Restore factory defaults and restart with a PRESET PLUG inserted
If you reset a device to the factory defaults, when the device restarts an inserted PRESET
PLUG is
formatted and the PRESET PLUG functionality is lost. You then need to create a
new PRESET PLUG. The keys stored on the KEY
-PLUG for releasing functions are
retained.
We recommend that you remove the PRESET PLUG before you reset the device to the
factory s
ettings.
Formatting a PRESET-PLUG (resetting the preset function)
You format the PRESET PLUG using the Command Line Interface (CLI) to reset the preset
function. To do this, follow the steps outlined below:
1. Start the remote configuration using Telnet (CLI) and log on with a user with the "admin"
role.
2. Change to the Global configuration mode with the command "configure terminal".
3. You change to the PLUG configuration mode with the "plug" command.
4. Enter the command "factoryclean".
The PRESET-PLUG is formatted and the preset function is reset.
5. Write the current configuration of the device with the "write" command.