Siemens Commissioning Guide CM1G5192en
Building Technologies 3 Mechanical installation 29.07.2010
3 Mechanical installation
3.1 Mounting
3.1.1 Drilling plan for SED2 IP20
H
H
H
W
W
Frame size A
Frame size B and C
Frame size D, E and F
5192M01en
Spacing
Frame size
H in mm W in mm
Mounting material
Tightening
torque
A
160
* 187
-
* 56
2 x M4 screws
2 x M4 lock washers
2
x M4 washers
2 x M4 nuts
or mounting on DIN rail
2.5 Nm
B
174
* 200
138
* 120
4
x M4 screws
4 x M4 lock washers
4
x M4 washers
4
x M4 nuts
2.5 Nm
C
204
* 232
174
* 156
4 x M5
screws
4 x M5 lock washers
4 x M5
washers
4 x M5
nuts
3.0 Nm
D
486 235
4 x M8
screws
4 x M8 lock washers
4 x M8
washers
4 x M8
nuts
13 Nm
E
616.4 235
4 x M8
screws
4 x M8 lock washers
4 x M8
washers
4 x M8
nuts
13 Nm
F
810
1110 with filter
300
4 x M8
screws
4 x M8 lock washers
4 x M8
washers
4 x M8
nuts
25 Nm
* With footprint filter

Table of Contents