Communication
2.2 Modbus
26 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.6.3 Data Type - Indications (Read)
The Indications data type is represented by two bits in holding registers:
Where:
Q: status/quality bit: 0 = OK, 1 = invalid
V: Value bit: 0 = OFF, 1 = ON
Status or Quality Bit Q
If the indication is invalid, the quality bit is set to 1. The value bit can be ignored in this case.
Example: The power frequency is invalid if the voltage is smaller than 15 % of the rated voltage when
measuring the frequency. Any limit violation indication based on this value is also invalid.
Value Bit V
The value bit indicates whether an indication is ON (=1) or OFF (=0).
2.2.6.4 Data Type - Controllable Indications (Read and Write)
The Controllable Indications data type is needed for:
The binary outputs of the SICAM Q100
Processing internal device commands (for example resetting the energy counters).
The holding register is used for read and write access in this context.
Use as Read Register
Where:
Q: status/quality bit: 0 = OK, 1 = invalid
V: Value bit: 0 = OFF, 1 = ON
See also chapter 2.2.6.3.
Q
for example Holding register 0101
V
Indication 8
Q V
Indication 7
Q V
Indication 1
Q V
Indication 2
Q V
Indication 3
Q V
Indication 4
Q V
Indication 5
Q V
Indication 6
Q
Holding register 0141
V
Indication 8
Q V
Indication 7
Q V
Indication 1
Q V
Indication 2
Q V
Indication 3
Q V
Indication 4
Q V
Indication 5
Q V
Indication 6
SYS_SICAM_Q100_US.book Page 26 Thursday, September 24, 2020 1:17 PM