Communication
2.2 Modbus
30 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
•Register 14001 to 14378: Harmonic power - reactive power value (read only)
•Register 15001 to 15378: Harmonic power - apparent power value (read only)
• Register 23001 to 27608: Energy profile (read only)
• Registers 30001 to 30032: Measured values for the Wind Farm mode (read only)
*)
See the following note:
Example:
If the average values of the harmonics of the voltage at the phases a, b, and c must be read, 3 requesting te-
legrams must be sent. Each of these telegrams contains the register range entered for these values (or a part
of it) for phases a, b, and c.
In SICAM PQS, the user must define different corresponding requesting groups for this, for example:
Figure 2-5 Settings in SICAM PQS
NOTE
For the access to measured values, the measured values read with a telegram must be exclusively in this ran-
ge. The addressed address range in a requesting telegram must not exceed the register range or fall below
this range.
SYS_SICAM_Q100_US.book Page 30 Thursday, September 24, 2020 1:17 PM