Communication
2.2 Modbus
40 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.15 Register 0153: Synchronization of Load Profile Measuring Period (Read and
Write)
Data type: Controllable indications
2.2.7.16 Register 0154: Tariffs (Read and Write)
Data type: Controllable indications
2.2.7.17 Registers 0201 to 0390, and 6401 to 6484: Measured Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value
Tabelle 2-19 Register 0153: Synchronization of Load Profile Measuring Period
Register Type of Information Remark
0153 Synchronization of load profile
measuring period
Value is given in minutes and lays between 1 an 60.
The value in the register must equal the paramete-
rized value. Otherwise, an error message is gene-
rated.
Table 2-20 Register 0154: Tariffs
Register Type of Information Remark
0154 Write:
the tariff valid from the next measuring period
on.
Read: currently valid tariff.
Value corresponds to tariff 1 through 8.
Table 2-21 Registers 0201 to 0390, and 6401 to 6484: Measured Values
Register Type of Information Remark Unit
0201 Va Voltage a-N V
0203 Vb Voltage b-N V
0205 Vc Voltage c-N V
0207 VN Voltage neutral conductor V
0209 Ia Current a A
0211 Ib Current b A
0213 Ic Current c A
SYS_SICAM_Q100_US.book Page 40 Thursday, September 24, 2020 1:17 PM