Communication
2.2 Modbus
39SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.13 Register 0151: Load Profiles (Write Only)
Data type: Control
2.2.7.14 Register 0152: Load Profiles (Read Only)
Data type: Indication
Table 2-17 Register 0151: Load Profiles
Register Type of Information Remark
0151/2
0
Reset load profile recording 0 1: resets the load profile buffer.
0151/2
2
to
0151/2
14
Reserved = 0
Table 2-18 Register 0152: Load Profiles
Register Type of Information Remark
0152/2
0
Sync missing Synchronization of the periods missing (indication
can only occur when the binary inputs are parame-
terized or via protocol).
0152/2
2
Resynchronized Following device startup, a synchronization instant
is calculated first. This instant does not have to be
correct in case of external synchronization. If the
synchronization is then performed via binary input
or communication and the instant calculated inter-
nally differs from it, the period synchronization is re-
synchronized accordingly to the external source.
0152/2
4
Load Profile Period Closed Indication for closing a subperiod/measuring period
0152/2
6
to
0152/2
14
Reserved = 0