Communication
2.2 Modbus
38 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.12 Registers 0141 to 0150: Indications and Commands of the Communication
(Read and Write)
Data type: Controllable indications
Table 2-16 Registers 0141 to 0150: Indications and Commands of the Communication
Register Type of Information Remark
0141/2
0
Indication 1 from Remote Controllable indications for binary outputs in the
SICAM Q100.
Indication can also be used to control LEDs of device or
can be integrated into a group indication.
0141/2
2
Indication 2 from Remote
0141/2
4
Reserved = 0
0141/2
6
Reset MSV Event
Send binary value “10” to reset PQ Voltage Event and
Energy Counters.
0141/2
8
Reset PQ Voltage Event
0141/2
10
Reset PQ Frequency Event
0141/2
12
Reset PQ VoltUnbal Event
0141/2
14
Reset Energy
0142/2
0
Indication 3 from Remote Controllable indications for binary outputs in the SICAM IO
subdevices.
Indications can also be used to control LEDs of device or
can be integrated into a group indication.
0142/2
2
Indication 4 from Remote
0142/2
4
Indication 5 from Remote
0142/2
6
Indication 6 from Remote
0142/2
8
Indication 7 from Remote
0142/2
10
Indication 8 from Remote
0142/2
12
Indication 9 from Remote
0142/2
14
Indication 10 from Remote
0143/2
0
Indication 11 from Remote
0143/2
2
Indication 12 from Remote
0143/2
4
Indication 13 from Remote
0143/2
6
Indication 14 from Remote
0143/2
8
to
0150/2
14
Reserved = 0