Communication
2.2 Modbus
37SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.11 Register 0136 and 0138: Status of Binary Outputs (BO) of SICAM IO
Subdevice (Read Only)
This register is write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
The following table shows the BO status of the SICAM IO subdevice 1 (0136). The BO status of the SICAM IO
subdevice 2 (0138) are in the same structure.
Table 2-15 Register 0136: Status of Binary Outputs of SICAM IO Subdevice 1
Register Type of Information Remark
0136/2
0
Binary output 1-N SICAM IO 1,
terminals N1/2
The statuses of the binary outputs are read from the
SICAM IO 7XV5673 connected as subdevice 1.
Value = 0 and status = invalid are transmitted when the
indication Subdevice 1 OK = 0.
The communication to SICAM IO 7XV5673 is inter-
rupted.
0136/2
2
Binary output 2-N SICAM IO 1,
terminals N3/4
0136/2
4
Binary output 3-N SICAM IO 1,
terminals N5/6
0136/2
6
Binary output 1-P SICAM IO 1,
terminals P1/2
0136/2
8
Binary output 2-P SICAM IO 1,
terminals P3/4
0136/2
10
Binary output 3-P SICAM IO 1,
terminals P5/6
0136/2
12
Reserved = 0
0136/2
14
Reserved = 0