Communication
2.2 Modbus
36 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
The following table shows the BI status of the SICAM IO subdevice 1 (0135). The BI status of the SICAM IO
subdevice 2 (0137) are in the same structure.
Table 2-14 Register 0135: Status of Binary Inputs of SICAM IO Subdevice 1
Register Type of Information Remark
0135/2
0
Binary input 1-N SICAM IO 1,
terminals N8/9
The statuses of the binary inputs are read from the
SICAM IO 7XV5673 connected as subdevice 1.
Value = 0 and status = invalid are transmitted when the
indication Subdevice 1 OK = 0.
The communication to SICAM IO 7XV5673 is inter-
rupted.
0135/2
2
Binary input 2-N SICAM IO 1,
terminals N9/10
0135/2
4
Binary input 3-N SICAM IO 1,
terminals N11/12
0135/2
6
Binary input 1-P SICAM IO 1,
terminals P8/9
0135/2
8
Binary input 2-P SICAM IO 1,
terminals P9/10
0135/2
10
Binary input 3-P SICAM IO 1,
terminals P11/12
0135/2
12
Reserved = 0
0135/2
14
SICAM Subdevice 1 OK Communication with the SICAM IO 7XV5673 is:
0 = interrupted
1 = established