Communication
2.2 Modbus
35SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.8 Register 0131: Status of the Binary Outputs (Read Only)
This register is write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
2.2.7.9 Register 0132: Status of the Binary Inputs (Read Only)
This register is write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
2.2.7.10 Register 0135 and 0137: Status of Binary Inputs (BI) of SICAM IO Subdevice
(Read Only)
This register is write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
Table 2-12 Register 0131: Status of the Binary Outputs
Register Type of Information Remark
0131/2
0
Binary Output B1 Binary output B1 at terminal G1/2
0131/2
2
Binary Output B2 Binary output B2 at terminal G3/2
0131/2
4
to
0131/2
14
Reserved = 0
Table 2-13 Register 0132: Status of the Binary Inputs
Register Type of Information Remark
0132/2
0
Binary Input B1 Binary output B1 at terminal U1/2
0132/2
2
Binary Input B2 Binary output B2 at terminal U3/2
0132/2
4
to
0132/2
14
Reserved = 0