Communication
2.2 Modbus
34 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.6 Register 0113: Group Indications (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
2.2.7.7 Register 0114: Power Quality Event (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
Table 2-10 Register 0113: Group Indications
Register Type of Information Remark
0113/2
0
Group indication 1 Up to 4 single-point indications can be linked logically and
combined to a group indication. A total of 4 group indications
can be parameterized:
0 = Off
1 = On
0113/2
2
Group indication 2
0113/2
4
Group indication 3
0113/2
6
Group indication 4
0113/2
8
Reserved = 0
0113/2
10
Reserved = 0
0113/2
12
Reserved = 0
0113/2
14
Reserved = 0
Table 2-11 Register 0114: Power Quality Event
Register Type of Information Remark
0114/2
0
PQ Volt event 1 = Voltage event exists
0 = Voltage event does not exist
0114/2
2
PQ Freq event 1 = Frequency event exists
0 = Frequency event does not exist
0114/2
4
PQ VoltUnbal event 1 = Voltage unbalance event exists
0 = Voltage unbalance event does not exist
0114/2
6
to
0114/2
14
Reserved = 0
NOTE
If a voltage, frequency or voltage unbalance event happened and ended, the relevant bit of this register will
be set to "1" and will be kept until it is reset by using relevant bits in register 141.
SYS_SICAM_Q100_US.book Page 34 Thursday, September 24, 2020 1:17 PM