Communication
2.2 Modbus
33SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.5 Registers 0111 and 0112: Measurand Limit Violation Indications (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
NOTE
Registers between 0103 and 0140 that are not shown can be read too during requests and return the value 0.
Table 2-9 Registers 0111 and 0112: Limit Violation Indications
Register Type of Information Remark
0111/2
0
Limit Violation 1 An indication is output (= 1) if a measured value has exceed-
ed or fallen below a configured limiting value. For more infor-
mation, see the SICAM Q100 device manual, chapter 8.
0111/2
2
Limit Violation 2
0111/2
4
Limit Violation 3
0111/2
6
Limit Violation 4
0111/2
8
Limit Violation 5
0111/2
10
Limit Violation 6
0111/2
12
Limit Violation 7
0111/2
14
Limit Violation 8
0112/2
0
Limit Violation 9 An indication is output (= 1) if a measured value has exceed-
ed or fallen below a configured limiting value. For more infor-
mation, see the SICAM Q100 device manual, chapter 8.
0112/2
2
Limit Violation 10
0112/2
4
Limit Violation 11
0112/2
6
Limit Violation 12
0112/2
8
Limit Violation 13
0112/2
10
Limit Violation 14
0112/2
12
Limit Violation 15
0112/2
14
Limit Violation 16