Communication
2.2 Modbus
46 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.19 Registers 0392 to 0399: Data/Time for Last Period PQ Calculation (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Registers 0392 to 0395: Data/Time for Last Period PQ Calculation
Data type: Data/time
Registers 0396 to 0399: Data/Time for Last Period PQ Calculation for Frequency (Configurable Period = 30 s to 2 h)
Data type: Data/time
Table 2-23 Registers 0392 to 0395: Data/Time for Last Period PQ Calculation
Register Type of Information Remark
0392 Milliseconds see chapter 2.2.6.2
0393 Hours/minutes
0394 Month/day
0395 Time status/year
Table 2-24 Registers 0396 to 0399: Data/Time for Last Period PQ Calculation for Frequency
Register Type of Information Remark
0396 Milliseconds see chapter 2.2.6.2
0397 Hours/minutes
0398 Month/day
0399 Time status/year