Communication
2.2 Modbus
47SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.20 Registers 0401 to 0514, 0777 to 0778, 0783 to 0784, and 16001 to 16006: PQ
Measured Values, Average Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
The data are calculated within the parameterized time (for example 30 s, 1 min etc.).
Data type: Measured value
Table 2-25 Registers 0401 to 0514, 0777 to 0778, 0783 to 0784, and 16001 to 16006: PQ Measured
Values – Average Values
Register Type of Information Remark Unit
0401 PQ_Va Voltage a-N V
0403 PQ_Vb Voltage b-N V
0405 PQ_Vc Voltage c-N V
0407 PQ_Vab Voltage a-b V
0409 PQ_Vbc Voltage b-c V
0411 PQ_Vca Voltage c-a V
0413 PQ_Ia Current a A
0415 PQ_Ib Current b A
0417 PQ_Ic Current c A
0419 PQ_VN Voltage neutral conductor V
0421 PQ_Vavg Mean value of voltage (P-N) V
0423 PQ_IN Current neutral conductor A
0425 PQ_Iavg Mean value of currents A
0427 PQ_Pa Active power a W
0429 PQ_Pb Active power b W
0431 PQ_Pc Active power c W
0433 PQ_P Active power W
0435 PQ_Qa Reactive power a var
0437 PQ_Qb Reactive power b var
0439 PQ_Qc Reactive power c var
0441 PQ_Q Reactive Power var
SYS_SICAM_Q100_US.book Page 47 Thursday, September 24, 2020 1:17 PM