Communication
2.2 Modbus
57SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
Registers 0807 to 0846: Counter Pulses
Data type: Counter
0804/2
14
Energy_Counters_Status_16 Status of counters WQ_cap -
0805/2
0
Energy_Counters_Status_17 Status of counters WSa -
0805/2
2
Energy_Counters_Status_18 Status of counters WSb -
0805/2
4
Energy_Counters_Status_19 Status of counters WSc -
0805/2
6
Energy_Counters_Status_20 Status of counters WS -
0805/2
8
to
0805/2
15
Reserved = 0 -
0806 Reserved = 0 -
Table 2-29 Registers 0803 to 0806: Counter Value Status (cont.)
Register Type of Information Remark Unit
Table 2-30 Registers 0807 to 0846: Counter Pulses
Register Type of Information Remark Unit
0807 WPa_imp Active Energy, Import, Phase A Pulse
0809 WPb_imp Active Energy, Import, Phase B Pulse
0811 WPc_imp Active Energy, Import, Phase C Pulse
0813 WP_imp Active Energy, Import Pulse
0815 WPa_exp Active Energy, Export, Phase A Pulse
0817 WPb_exp Active Energy, Export, Phase B Pulse
0819 WPc_exp Active Energy, Export, Phase C Pulse
0821 WP_exp Active Energy, Export Pulse
0823 WQa_ind Reactive Energy, Inductive, Phase A Pulse
0825 WQb_ind Reactive Energy, Inductive, Phase B Pulse
0827 WQc_ind Reactive Energy, Inductive, Phase C Pulse
0829 WQ_ind Reactive Energy, Inductive Pulse
0831 WQa_cap Reactive Energy, Capacitive, Phase A Pulse
0833 WQb_cap Reactive Energy, Capacitive, Phase B Pulse
SYS_SICAM_Q100_US.book Page 57 Thursday, September 24, 2020 1:17 PM