Communication
2.2 Modbus
59SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.25 Registers 1001 to 1378: Harmonics - Voltage Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Network types: harmonic ph-n is available if 4-wire is used, and harmonic ph-ph is available if 3-wire is used.
Data type: Measured value
2.2.7.26 Registers 1379 to 1756: Harmonics - Current Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Data type: Measured value
Table 2-33 Registers 1001 to 1378: Harmonics - Voltage Values
Register Type of Information Remark Unit
1001 H_Va-1/H_Vab-1 Harmonic, voltage value, a-N, ab
(fundamental)
V
1003 to 1126 H_Va-x/H_Vab-x
(x = 2 to 63)
Harmonic, voltage value, a-N, ab
(2 bytes for each register)
V/%
1127 H_Vb-1/H_Vbc-1 Harmonic, voltage value, b-N, bc
(fundamental)
V
1129 to 1252 H_Vb-x/H_Vbc-x
(x = 2 to 63)
Harmonic, voltage value, b-N, bc
(2 bytes for each register)
V/%
1253 H_Vc-1/H_Vca-1 Harmonic, voltage value, c-N, ca
(fundamental)
V
1255 to
1378
H_Vc-x/H_Vca-x
(x = 2 to 63)
Harmonic, voltage value, a-N, ab
(2 bytes for each register)
V/%
Table 2-34 Registers 1379 to 1756: Harmonics - Current Values
Register Type of Information Remark Unit
1379 H_Ia-1 Harmonic, current value, a
(fundamental)
A
1381 to
1504
H_Ia-x
(x = 2 to 63)
Harmonic,current value, a
(2 bytes for each register)
A
1505 H_Ib-1 Harmonic, current value, b
(fundamental)
A
1507 to
1630
H_Ib-x
(x = 2 to 63)
Harmonic,current value, b
(2 bytes for each register)
A
SYS_SICAM_Q100_US.book Page 59 Thursday, September 24, 2020 1:17 PM