Communication
2.2 Modbus
65SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.33 Registers 4001 to 4378: Phase Angle of Harmonics - Voltage Values (Read
Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
2.2.7.34 Registers 4379 to 4756: Phase Angle of Harmonics - Current Values (Read
Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
3445 WS_tariff_value_1 Apparent Energy, Tariff 1 VAh
Table 2-41 Registers 3301 to 3448: Values of Tariff 1
Register Type of Information Remark Unit
Table 2-42 Registers 4001 to 4378: Phase Angle of Harmonics - Voltage Values
Register Type of Information Remark Unit
4001 HP_Va-1
Harmonic (phase angle), voltage value, a-N
(fundamental)
° (degree)
4003 to
4126
HP_Va-x
(x = 2 to 63)
Harmonic (phase angle), voltage value, a-N
(2 bytes for each register)
° (degree)
4127 HP_Vb-1
Harmonic (phase angle), voltage value, b-N
(fundamental)
° (degree)
4129 to
4252
HP_Vb-x
(x = 2 to 63)
Harmonic (phase angle), voltage value, b-N
(2 bytes for each register)
° (degree)
4253 HP_Vc-1
Harmonic (phase angle), voltage value, c-N
(fundamental)
° (degree)
4255 to
4378
HP_Vc-x
(x = 2 to 63)
Harmonic (phase angle), voltage value, c-N
(2 bytes for each register)
° (degree)
SYS_SICAM_Q100_US.book Page 65 Thursday, September 24, 2020 1:17 PM