EasyManua.ls Logo

Siemens SICAM Q100 - Page 64

Siemens SICAM Q100
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
2.2 Modbus
64 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.32 Registers 3301 to 3756: Tariff Values (Read Only)
Data type: Measured value
The following table shows the general information (3301 to 3304) and values for the tariff 1 (3405 to 3448). The
values of the other 7 tariffs (3449 to 3756) are in the same structure.
3201 H_Ic-1_MAX
Harmonic (average value), current value, c
(Fundamental)
A
3203 to
3298
H_Ic-x_MAX
(x = 2 to 49)
Harmonic (average value), current value, c
(2 bytes for each register)
A
Table 2-40 Registers 3001 to 3298: PQ Calculation for Maximum Harmonics - Current Values
Register Type of Information Remark Unit
NOTE
Registers 3301 to 3756 are not available in SICAM PQS.
Table 2-41 Registers 3301 to 3448: Values of Tariff 1
Register Type of Information Remark Unit
3301 Milliseconds see chapter 2.2.6.2 -
3302 Hours/minutes -
3303 Month/day -
3304 Time status/year -
3405 WP_exp_tariff_value_1 Active Energy, Export, Tariff 1 Wh
3409 WP_imp_tariff_value_1 Active Energy, Import, Tariff 1 Wh
3413 WQ_ind_imp_tariff_value_1 Reactive Energy, Inductive, Import, Tariff 1 varh
3417 WQ_cap_exp_tariff_value_1 Reactive Energy, Capacitive, Export, Tariff 1 varh
3421 WQ_ind_exp_tariff_value_1 Reactive Energy, Inductive, Export, Tariff 1 varh
3425 WQ_cap_imp_tariff_value_1 Reactive Energy, Capacitive, Import, Tariff 1 varh
3429 WQ_ind_tariff_value_1 Reactive Energy, Inductive, Tariff 1 varh
3433 WQ_cap_tariff_value_1 Reactive Energy, Capacitive, Tariff 1 varh
3437 WQ_imp_tariff_value_1 Reactive Energy, Import, Tariff 1 varh
3441 WQ_exp_tariff_value_1 Reactive Energy, Export, Tariff 1 varh