Communication
2.2 Modbus
71SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.41 Registers 6101 to 6158: Load Profile – Measured Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value
LOADPROFILE_FLAG_Q1 0x00000040 Reactive power = Q1
LOADPROFILE_FLAG_QTOT 0x00000020 Reactive power = Qtot
LOADPROFILE_FLAG_QMIXED 0x00000010 Reactive power was changed
in subperiod
Table 2-50 Last period information - Flags (cont.)
Type of Flags Flag Remark
Table 2-51 Registers 6101 to 6158: Load Profile – Measured Values
Register Type of Information Unit
6101 Total power factor import (previous period) -
6103 Total power factor export (previous period) -
6105 Average active power import (previous period) W
6107 Average active power export (previous period) W
6109 Average reactive power import (previous period) var
6111 Average reactive power export (previous period) var
6113 Average apparent power (previous period) VA
6115 Cumulated active power import (previous period) W
6117 Cumulated active power export (previous period) W
6119 Cumulated reactive power import (previous period) var
6121 Cumulated reactive power export (previous period) var
6123 Cumulated apparent power (previous period) VA
6125 Maximum active power (previous period) W
6127 Minimum active power (previous period) W
6129 Maximum reactive power (previous period) var
6131 Minimum reactive power (previous period) var
SYS_SICAM_Q100_US.book Page 71 Thursday, September 24, 2020 1:17 PM