Communication
2.2 Modbus
70 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.40 Registers 6087 to 6100: Load Profile – Management (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Unsigned, long
Table 2-49 Registers 6087 to 6100: Load Profile – Management
Register Type of Information Remark
6087 to 6090 Timestamp of last terminated period UTC format
6091 to 6092 Momentary record ID (RecID) Value of the momentary load profile identifier
6093 to 6094 Length of last terminated period Unit: s
6095 to 6096 Time since begin of momentary period Unit: s
6097 to 6098 Duration of subinterval Unit: ms
6099 to 6100 Last period information Meaning of the flags: see following table
Table 2-50 Last period information - Flags
Type of Flags Flag Remark
LOADPROFILE_FLAG_QUALITY_UNSECURE 0x00800000 Power values not exact
because of overflow of at
least one current or voltage
value
LOADPROFILE_FLAG_QUALITY_AUXPOWER_FAIL 0x00400000 Power supply failure
LOADPROFILE_FLAG_QUALITY_SYNC 0x00200000 Time synchronization may not
be accurate, for example,
because the time has not
been updated yet.
LOADPROFILE_FLAG_MISSUB 0x00100000 Flag "missing subinterval" for
modbus communication
LOADPROFILE_FLAG_QUALITY_PERIOD_TO_SHORT 0x00010000 Resynch period is shorter
than parameterized
LOADPROFILE_TEMP_SYNCED 0x00000100 The flag is set if the period
was synchronized internally;
the external synchronization
(binary inputs, communica-
tion) has not been received
yet.
LOADPROFILE_FLAG_QN 0x00000080 Reactive Power = Qn