Communication
2.2 Modbus
69SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.39 Registers 6001 to 6032: Number of PQ Events (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Table 2-48 Registers 6001 to 6032: Number of PQ Events
Register Type of Information Remark
6001 PQ_Event_Number Total number of PQ voltage events
6003 PQ_Event_Lnumber Number of PQ voltage events since last polling
6005 Dip_Event_Number Total number of PQ dip events
6007 Dip_Event_Lnumber Number of PQ dip events since last polling
6009 Swell_Event_Number Total number of PQ swell events
6011 Swell_Event_Lnumber Number of PQ swell events since last polling
6013 Interrupt_Event_Number Total number of PQ interrupt events
6015 Interrupt_Event_Lnumber Number of PQ interrupt events since last polling
6017 RVC_Event_Number Total number of PQ RVC events
6019 RVC_Event_Lnumber Number of PQ RVC events since last polling
6021 Transient_Event_Number Total number of PQ transient events
6023 Transient_Event_Lnumber Number of PQ transient events since last polling
6025 Volunb_Event_Number Total number of PQ voltage-unbalanced events
6027 Volunb_Event_Lnumber Number of PQ voltage-unbalanced events since last
polling
6029 Freq_Event_Number Total number of PQ frequency events
6031 Freq_Event_Lnumber Number of PQ frequency events since last polling