Communication
2.2 Modbus
76 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.47 Registers 8401 to 8408: Indications from Modbus Slave Devices (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
The following table shows the indications from the Modbus slave device 1 (8401). The indications from the oth-
er 7 Modbus slave devices (8402 to 8408) are in the same structure.
2.2.7.48 Registers 10001 to 10378: Prevailing Ratio of Harmonics – Voltage Values
(Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Reference rate: Aggregation time
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
Tabelle 2-57 Register 8401: Indications from Modbus Slave Devices
Register Type of Information Remark
8401/2
0
Ind. 1 from device 1 Indications 1 to 6 from Modbus slave device 1
8401/2
2
Ind. 2 from device 1
8401/2
4
Ind. 3 from device 1
8401/2
6
Ind. 4 from device 1
8401/2
8
Ind. 5 from device 1
8401/2
10
Ind. 6 from device 1
8401/2
12
Reserved = 0
8401/2
14
Reserved = 0
Table 2-58 Registers 10001 to 10378: Prevailing Ratio of Harmonics – Voltage Values
Register Type of Information Remark Unit
10001 HPR_Va-1
Harmonic (prevailing ratio), voltage value, a-N
(fundamental)
° (degree)
10003 to
10126
HPR_Va-x
(x = 2 to 63)
Harmonic (prevailing ratio), voltage value, a-N
(2 bytes for each register)
° (degree)
10127 HPR_Vb-1
Harmonic (prevailing ratio), voltage value, b-N
(fundamental)
° (degree)
SYS_SICAM_Q100_US.book Page 76 Thursday, September 24, 2020 1:17 PM