Communication
2.2 Modbus
77SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.49 Registers 10379 to 10756: Prevailing Ratio of Harmonics – Current Values
(Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Reference rate: Aggregation time
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
10129 to
10252
HPR_Vb-x
(x = 2 to 63)
Harmonic (prevailing ratio), voltage value, b-N
(2 bytes for each register)
° (degree)
10253 HPR_Vc-1
Harmonic (prevailing ratio), voltage value, c-N
(fundamental)
° (degree)
10255 to
10378
HPR_Vc-x
(x = 2 to 63)
Harmonic (prevailing ratio), voltage value, c-N
(2 bytes for each register)
° (degree)
Table 2-58 Registers 10001 to 10378: Prevailing Ratio of Harmonics – Voltage Values
Register Type of Information Remark Unit
Table 2-59 Registers 10379 to 10756: Prevailing Ratio of Harmonics – Current Values
Register Type of Information Remark Unit
10379 HPR_Ia-1
Harmonic (prevailing ratio), current value, a
(fundamental)
° (degree)
10381 to
10504
HPR_Ia-x
(x = 2 to 63)
Harmonic (prevailing ratio), current value, a
(2 bytes for each register)
° (degree)
10505 HPR_Ib-1
Harmonic (prevailing ratio), current value, b
(fundamental)
° (degree)
10507 to
10630
HPR_Ib-x
(x = 2 to 63)
Harmonic (prevailing ratio), current value, b
(2 bytes for each register)
° (degree)
10631 HPR_Ic-1
Harmonic (prevailing ratio), current value, c
(fundamental)
° (degree)
10633 to
10756
HPR_Ic-x
(x = 2 to 63)
Harmonic (prevailing ratio), current value, c
(2 bytes for each register)
° (degree)