Communication
2.2 Modbus
78 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.50 Registers 12001 to 12378: Phase Angle of Harmonics – Power (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
2.2.7.51 Registers 13001 to 13378: Harmonics, Power – Active Power Values (Read
Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
Table 2-60 Registers 12001 to 12378: Phase Angle of Harmonics – Power
Register Type of Information Remark Unit
12001 HP_a-1
Harmonic (phase angle), power, a-N
(fundamental)
° (degree)
12003 to
12126
HP_a-x
(x = 2 to 63)
Harmonic (phase angle), power, a-N
(2 bytes for each register)
° (degree)
12127 HP_b-1
Harmonic (phase angle), power, b-N
(fundamental)
° (degree)
12129 to
12252
HP_b-x
(x = 2 to 63)
Harmonic (phase angle), power, b-N
(2 bytes for each register)
° (degree)
12253 HP_c-1
Harmonic (phase angle), power, c-N
(fundamental)
° (degree)
12255 to
12378
HP_c-x
(x = 2 to 63)
Harmonic (phase angle), power, c-N
(2 bytes for each register)
° (degree)
Table 2-61 Registers 13001 to 13378: Harmonics, Power - Active Power Values
Register Type of Information Remark Unit
13001 HP_Pa-1
Harmonic (active power), a-N
(fundamental)
° (degree)
13003 to
13126
HP_Pa-x
(x = 2 to 63)
Harmonic (active power), a-N
(2 bytes for each register)
° (degree)