Communication
2.2 Modbus
79SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.52 Registers 14001 to 14378: Harmonics, Power – Reactive Power Values (Read
Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
13127 HP_Pb-1
Harmonic (active power), b-N
(fundamental)
° (degree)
13129 to
13252
HP_Pb-x
(x = 2 to 63)
Harmonic (active power), b-N
(2 bytes for each register)
° (degree)
13253 HP_Pc-1
Harmonic (active power), c-N
(fundamental)
° (degree)
13255 to
13378
HP_Pc-x
(x = 2 to 63)
Harmonic (active power), c-N
(2 bytes for each register)
° (degree)
Table 2-61 Registers 13001 to 13378: Harmonics, Power - Active Power Values
Register Type of Information Remark Unit
Table 2-62 Registers 14001 to 14378: Harmonics, Power - Reactive Power Values
Register Type of Information Remark Unit
14001 HP_Qa-1
Harmonic (reactive power), a-N
(fundamental)
° (degree)
14003 to
14126
HP_Qa-x
(x = 2 to 63)
Harmonic (reactive power), a-N
(2 bytes for each register)
° (degree)
14127 HP_Qb-1
Harmonic (reactive power), b-N
(fundamental)
° (degree)
14129 to
14252
HP_Qb-x
(x = 2 to 63)
Harmonic (reactive power), b-N
(2 bytes for each register)
° (degree)
14253 HP_Qc-1
Harmonic (reactive power), c-N
(fundamental)
° (degree)
14255 to
14378
HP_Qc-x
(x = 2 to 63)
Harmonic (reactive power), c-N
(2 bytes for each register)
° (degree)
SYS_SICAM_Q100_US.book Page 79 Thursday, September 24, 2020 1:17 PM