80 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.53 Registers 15001 to 15378: Harmonics, Power – Apparent Power Values (Read
Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Calculation period: 10/12 cycle (50Hz/60Hz)
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
Table 2-63 Registers 15001 to 15378: Harmonics, Power - Apparent Power Values
Register Type of Information Remark Unit
15001 HP_Sa-1
Harmonic (apparent power), a-N
(fundamental)
° (degree)
15003 to
15126
HP_Sa-x
(x = 2 to 63)
Harmonic (apparent power), a-N
(2 bytes for each register)
° (degree)
15127 HP_Sb-1
Harmonic (apparent power), b-N
(fundamental)
° (degree)
15129 to
15252
HP_Sb-x
(x = 2 to 63)
Harmonic (apparent power), b-N
(2 bytes for each register)
° (degree)
15253 HP_Sc-1
Harmonic (apparent power), c-N
(fundamental)
° (degree)
15255 to
15378
HP_Sc-x
(x = 2 to 63)
Harmonic (apparent power), c-N
(2 bytes for each register)
° (degree)
SYS_SICAM_Q100_US.book Page 80 Thursday, September 24, 2020 1:17 PM