Communication
2.2 Modbus
81SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.54 Registers 23001 to 27608: Latest 288 Energy Profiles (Read Only)
You can read the data of the energy profiles during the latest 288 intervals via the Modbus TCP registers. These
registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Date type: Measured value +Date/time
The following table shows the data of the energy profile during the latest interval (23001 to 23016). The data
of the energy profiles during the other 287 intervals (23017 to 27608) are in the same structure.
Table 2-64 Registers 23001 to 23016: The Latest 288 Energy Profiles (During the Latest Interval)
Register Type of Information Unit Remark
23001 Milliseconds End time of energy profile
For data format, see chapter 2.2.6.2.
23002 Hours/minutes
23003 Month/day
23004 Year
23005 to 23006 WP_exp kWh Active energy export
23007 to 23008 WQ_exp kVARh Reactive energy export
23009 to 23010 WP_imp kWh Active energy import
23011 to 23012 WQ_imp kVARh Reactive energy import
23013 to 23014 WS kVAh Apparent energy
23015 Quality - bit 0 = 1: The energy profile is not calculated.
bit 0 = 0: The energy profile is calculated.
bit 1 = 1: Auxiliary power fails.
bit 1 = 0: Auxiliary power works well.
bit 2 = 1: Device starts up.
bit 2 = 0: Device works well.
bit 3 = 1: Time jumps.
bit 3 = 0: Time does not jump.
23016 Reserved -