Technical specifications
Flat Panel
24 Operating Instructions (Compact), 09/2008, A5E02313712-01
EMC
Standard
EMC requirements EN 61000-6-4
EN 61000-6-2
Area of application: The device is designed for
industrial use.
Radio frequency interference EN 55011 Class A, Group 1
Immunity level against very steep impulses: Bursts
Interference immunity on power lines
Interference immunity on data and signal lines <30
m
Immunity in data/signal lines >30 m process data
lines
EN 61000-4-4 24 DC V; 2.0 kV,
interference criterion B
2.0 kV, interference criterion B
2.0 kV, interference criterion B
Immunity to surges: Surge EN 61000-4-5 On 24 V DC: 0.5 kV symmetric, asymmetric
1 kV symmetric
2 kV asymmetric
Immunity to discharge of static electricity ESD EN 61000-4-2 |8 kV with air discharge
4 kV on contact, direct/indirect
Interference criterion B
Interference immunity against radiated, radio-
frequency, electromagnetic fields
EN 61000-4-3 80-1000 MHz: 10 V/m
Modulation: 80 % AM with 1 kHz, interference
criterion A
HF radiation in cables and cable shields EN 61000-4-6 On 24 V DC: 10 V
On signal lines and data lines
150 kHz to 80 MHz: 10 V
Modulation: 80 % AM with 1 kHz, interference
criterion A
Interference immunity against magnetic fields EN 61000-4-8 50/60 Hz, 30 A/m effective value