4.5.2 Connecting PROFINET IO via the BusAdapter
Requirement
• The PROFINET IO cables are assembled (ber-optic cables are connected to LC connectors).
• If the device is the last node of the ber-optic network, the unused ber-optic interface is
closed with a blanking plug.
Note
In the factory state, the blanking plugs are inserted in the PROFINET sockets of the
BusAdapter.
NOTICE
Derating when using a redundant ET 200SP HA
When using a redundant ET 200SP HA, read the information about the permissible ambient
temperature.
Required accessories
• FC FO Termination Kit; for the FC LC plug when the IE FC FO cable is assembled with the IE FC
LC plug
CAUTION
Cleaving the glassber
• Wear protective glasses during the cleaving process.
• Dispose of the remaining bers in a suitable waste container.
• LC plug connector for PROFINET connection: IE FC LC Plug (10 duplex plugs:
6GK1900-1RB00-2AB0)
• Cable with maximum length of 3 km:
Cable type Article number
FO Standard Cable GP 6XV1847-2A
FO Trailing Cable 6XV1847-2C
FO Robust Cable GP 6XV1873-5R
Required tools
Screwdriver:
• TORX T10
or
• 3.5 mm blade width
Installation
4.5 BusAdapter BA 2xLC
BusAdapter for Distributed I/O
Equipment Manual, 10/2021, A5E39261458-AC 23