What to do if there is DA/AD conversion error in Siemens I/O Systems?
- LLouis SheppardAug 1, 2025
If you are experiencing a DA/AD conversion error with your Siemens I/O Systems, indicated by the relevant channel being set to 7FFF H or 0 V, there are a few potential causes. First, check that the load voltage is 24 V or, at the very least, above 10 V. Secondly, high-frequency interference may be disrupting the measuring signal, indicating a possible EMC problem. Finally, the A/D converter itself might be defective. In this case, have the module checked and repaired if necessary.