Data Exchange with the SM 335
3-13
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
6ES7 335-7HG00-8BA1
3.2.2 SM 335 parameters assignable with HW Config
Parameter assignment application
The STEP 7 tool used to initialize the analog modules in a STEP 7 environment is
called “HW Config”.
SM 335 parameters
Table 3-9 provides an overview of the SM 335 parameters which can be assigned
with HW Config.
Table 3-9 SM 335 parameters in HW Config
Parameters
SM 335
Value Range Default
Basic settings for inputs
• Hardware interrupt for end-of-cycle
• Diagnostic interrupt enable
yes/no
yes/no
no
no
Diagnostics for inputs: Enable
includes:
• Measuring range underrange
• Measuring range overrange
• Overrange of permitted common mode
voltage
yes/no no
Open-wire test yes/no no
Measurement
• Method Deactivated
Voltage
Current (4-wire trans-
ducer)
Voltage
• Range Voltage: " 1 V; " 2.5 V; 0 to 10 V;
0 V to + 2 V (channel CH0 to CH3)
default" 10 V;
Current: " 10 mA; 0 mA to + 20 mA
+ 4 mA to + 20 mA (channel CH2 to CH3)
• Cycle time for A/D conversion 0,5;
*)
1 to 16 ms 0.5 ms
*)
Diagnostics for outputs (short-circuit test) yes/no no
Response with CPU-STOP “Keep last value
(KLV)” or
“Output have no cur-
rent or voltage
(OCV)”
“Output have no
current or voltage
(OCV)”
*)
The setting 0.5 ms in HW Config means: Free Cycle
The setting of 1 to 16 ms in HW Config means: Conditional Cycle