Data Exchange with the SM 335
3-8
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
6ES7 335-7HG00-8BA1
3.1.3 Analog value representation for analog input channels
The tables contain representations of the measuring values of individual measuring
ranges of the analog inputs.
Table 3-5 Analog Value Representation in the Bipolar Input Ranges
Measuring Range
Units Range
+ 1 V + 10 V + 2.5 V + 10 mA decimal hexa-
decimal
1.185 V
:
:
11.851 V
:
:
2.963 V
:
:
11,85 mA
:
:
32767
:
32512
7FFF
H
:
7F00
H
Overflow
1,1758 V
:
:
11,758 V
:
:
2,938 V
:
:
11,758 mA
:
:
32508
:
27652
7EFC
H
:
6C04
H
Over-
range
1 V
:
0.75 V
:
144.68 µV
0 V
–144.68 µV
:
–0.75
:
–1 V
10 V
:
7.5 V
:
1446.8 µV
0 V
–1446.8 µV
:
–7.5 V
:
–10 V
2.5 V
:
1.875 V
:
361.69 µV
0 V
–361.69 µV
:
–1.875 V
:
–2.5 V
10 mA
:
7.5 mA
:
1446.8 nA
0 mA
–1446.8 nA
:
–7.5 mA
:
–10 mA
27648
:
20736
:
4
0
–4
:
–20736
:
–27648
6C00
H
:
5100
H
:
4
H
0
FFFC
H
:
AF00
H
:
9400
H
Rated
range
:
:
–1.176 V
:
:
–11.759 V
:
:
–2.940 V
:
:
–11.76 mA
–27652
:
–32512
93FC
H
:
8100
H
Under-
range
:
:
–1.185 V
:
:
–11.851 V
:
:
–2.963 V
:
:
–11.85 mA
–32516
:
–32768
80FC
H
:
8000
H
Underflow

Table of Contents