EasyManua.ls Logo

Siemens simatic ET 200MP - C.3 Representation of Analog Values in the Current Measuring Ranges

Siemens simatic ET 200MP
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Representation of analog values
C.2 Representation of analog values in voltage measuring ranges
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
54 Manual, 03/2019, A5E44792324-AA
C.2 Representation of analog values in voltage measuring ranges
The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table C- 4 Voltage measuring ranges ±10 V, ±5 V, ±1 V,
Values
Voltage measuring range
Range
dec
hex
±10 V
±5 V
±1 V
32767 7FFF >11.759 V >5.879 V > 1.176 V Overflow
32511
7EFF
11.759 V
5.879 V
1.176 V
Overshoot range
27649
6C01
27648
6C00
10 V
5 V
1 V
Rated range
20736
5100
7.5 V
3.75 V
0.75 V
1
1
361.7 µV
180.8 µV
36.17 µV
0
0
0 V
0 V
0 V
-1
FFFF
-20736
AF00
-7.5 V
-3.75 V
-0.75 V
-27648
9400
-10 V
-5 V
-1 V
-27649
93FF
Undershoot range
-32512
8100
-11.759 V
-5.879 V
-1.176 V
-32768
8000
< -11.759 V
< -5.879 V
< -1.176 V
Underflow
Table C- 5 Voltage measuring ranges ±500 mV and ±50 mV
Values
Voltage measuring range
Range
dec
hex
±500 mV
±50 mV
32767
7FFF
>587.9 mV
> 58.8 mV
Overflow
32511
7EFF
587.9 mV
58.8 mV
Overshoot range
27649
6C01
27648
6C00
500 mV
50 mV
Rated range
20736
5100
375 mV
37.5 mA
1
1
18.08 µV
1.81 µV
0
0
0 mV
0 mV
-1 FFFF
-20736
AF00
-375 mV
-37.5 mV
-27648 9400 -500 mV -50 mV
-27649
93FF
Undershoot range
-32512
8100
-587.9 mV
-58.8 mV
-32768
8000
<-587.9 mV
< -58.8 mV
Underflow

Other manuals for Siemens simatic ET 200MP