Representation of analog values
C.5 Measured values for wire break diagnostic
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
Manual, 03/2019, A5E44792324-AA
59
C.5 Measured values for wire break diagnostic
Measured values on diagnostic event "wire break", dependent on diagnostics enables
Error events initiate a diagnostics entry and trigger a diagnostics interrupt if configured
accordingly.
Table C- 14 Measured values for wire break diagnostic
Format
Parameter assignment
Measured values
Explanation
S7
"Wire break" diagnostics enabled
"Overflow/Underflow" diagnostics
enabled or disabled
("Wire break" diagnostics takes priority
over "Overflow/Underflow" diagnostics)
32767 7FFF
H
"Wire break" or "Open circuit" diagnostic
alarm
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
enabled
-32767 8000
H
Measured value after leaving the under-
shoot range
Diagnostic alarm "Low limit violated"
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
disabled
-32767 8000
H
Measured value after leaving the undershoot
range