Representation of analog values
C.4 Representation of the analog values of resistance-based sensors/resistance thermometers
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
58 Manual, 03/2019, A5E44792324-AA
Table C- 12 Thermal resistors Ni 100, Ni 1000, LG-Ni 1000 Standard
Ni x00
standard
in °C
(1 digit =
0.1 °C)
Values
Ni x00
Standard
in °F
(1 digit =
0.1 °F)
Values
Ni x00
Standard
in K
(1 digit =
0.1 K)
Values
Range
dec
hex
dec
hex
dec
hex
> 295.0
32767
7FFF
> 563.0
32767
7FFF
> 568.2
32767
7FFF
Overflow
295.0
:
250.1
2950
:
2501
B86
:
9C5
563.0
:
482.1
5630
:
4821
15FE
:
12D5
568.2
:
523.3
5682
:
5233
1632
:
1471
Overshoot
range
250.0
:
-60.0
2500
:
-600
9C4
:
FDA8
482.0
:
-76.0
4820
:
-760
12D4
:
FD08
523.2
:
213.2
5232
:
2132
1470
:
854
Rated range
-60.1
:
-105.0
-601
:
-1050
FDA7
:
FBE6
-76.1
:
-157.0
-761
:
-1570
FD07
:
F9DE
213.1
:
168.2
2131
:
1682
853
:
692
Undershoot
range
< -105.0
-32768
8000
< -157.0
-32768
8000
< 168.2
32768
8000
Underflow
Table C- 13 Thermal resistors Ni 100, Ni 1000, LG-Ni 1000 Climate
Ni x00 Climate in °C
(1 digit = 0.01 °C)
Values
Ni x00 Climate in
°F
(1 digit = 0.01 °F)
Values
Range
dec
hex
dec
hex
> 155.00
32767
7FFF
> 311.00
32767
7FFF
Overflow
155.00
:
130.01
15500
:
13001
3C8C
:
32C9
311.00
:
266.01
31100
:
26601
797C
:
67E9
Overshoot
range
130.00
:
-60.00
13000
:
-6000
32C8
:
E890
266.00
:
-76.00
26600
:
-7600
67E8
:
E250
Rated range
-60.01
:
-105.00
-6001
:
-10500
E88F
:
D6FC
-76.01
:
-157.00
-7601
:
-15700
E24F
:
C2AC
Undershoot
range
< - 105.00
-32768
8000
< - 157.00
-32768
8000
Underflow