Representation of analog values
C.4 Representation of the analog values of resistance-based sensors/resistance thermometers
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
Manual, 03/2019, A5E44792324-AA
57
The following tables list the decimal and hexadecimal values (codes) of the supported
resistance thermometers.
Table C- 10 Resistance thermometers Pt 100 and Pt 1000 Standard
Pt x00
Standard
in °C
(1 digit =
0.1°C)
Pt x00
Standard
in °F
(1 digit =
0.1 °F)
Pt x00
Standard
in K
(1 digit =
0.1 K)
1000.0
:
850.1
10000
:
8501
2710
:
2135
1832.0
:
1562.1
18320
:
15621
4790
:
3D05
1273.2
:
1123.3
12732
:
11233
31BC
:
2BE1
Overshoot
range
850.0
:
8500
:
2134
:
1562.0
:
15620
:
3D04
:
1123.2
:
11232
:
2BE0
:
Rated range
-200.1
:
-2001
:
F82F
:
-328.1
:
-3281
:
F32F
:
73.1
:
731
:
2DB
:
Undershoot
range
Table C- 11 Resistance thermometers Pt 100 and Pt 1000 Climate
Pt x00 Climate/ in
°C
(1 digit = 0.01 °C)
Pt x00 Climate/ in
°F
(1 digit = 0.01 °F)
155.00
:
15500
:
3C8C
:
311.00
:
31100
:
797C
:
Overshoot
range
130.00
:
13000
:
32C8
:
266.00
:
26600
:
67E8
:
Rated range
-120.01
:
-12001
:
D11F
:
-184.01
:
-18401
:
B81F
:
Undershoot