EasyManua.ls Logo

Siemens SIMATIC ET 200S - Addressing the ET 200 S Frequency Converter

Siemens SIMATIC ET 200S
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.2 Addressing the ET 200S frequency converter
Overview
Communication between the SIMOTION device and the ET 200S FC takes place through
direct access to the I/O. I/O variables are used to address the direct read/write access to the
I/O.
Creating I/O variables
For the cyclic data transfer with the ET 200S frequency converter, you must create an I/
O variable in the symbol browser for each I/O input and output. When creating the I/O variable,
enter the configured address from the hardware configuration in the "I/O address" column (see
example below). Enter a field length of 8 in the "Field length" column.
With these specifications, an I/O variable of type ARRAY[0..7] of BYTE is created in the
SIMOTION project for cyclic data transfer.
Example:
Determining addresses from HW Config:
Figure 3-1 Addresses in HW Config
Creating the I/O variables in the symbol browser:
Programming
3.2 Addressing the ET 200S frequency converter
Supplement for the ET 200S frequency converter
14 Function Manual, 01/2015

Other manuals for Siemens SIMATIC ET 200S

Related product manuals