CP 343-1 ERPC
Manual, 03/2010, C79000-G8976-C239-02
81
Error messages of the ERPC application
D
Error messages of the ERPC application
The table describes error messages that you will find in NCM S7 Diagnostics in the
"Application" diagnostic object. The errors coded in hexadecimal have the following
meaning:
Table D- 1 Meaning of the error coding
Code Meaning Meaning / notes
0080
h
deviceWISE was started.
0081
h
Missing time synchronization in the CP
configuration
Since time synchronization was not set in
the parameters, the time information of
the CP is wrong.
0082
h
Free memory capacity of the internal file
system of the CP is below <
value
> %
If this message is displayed, reduce the
amount of data for current transactions by
reducing the number of variables or the
length of arrays.
0083
h
Free memory capacity of the flash system of
the CP is below <
value
> %
If this message is displayed, reduce the
number of triggers or the data in the CP-
internal database.
0084
h
The "Attention bit" was set in deviceWISE. Group error that can be configured in
deviceWISE (see deviceWISE
documentation)
0085
h
Error no. <
value
> occurred in deviceWISE. (see deviceWISE documentation)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET CP 343-1 ERPC and is the answer not in the manual?

Siemens SIMATIC NET CP 343-1 ERPC Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET CP 343-1 ERPC
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals