EasyManuals Logo

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 User Manual

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
Application and properties
1.5 Configuration limits and performance data
CP 1243-1
16 Operating Instructions, 12/2016, C79000-G8976-C365-02
Frame memory (send buffer)
The CP has a frame memory (send buffer) for the values of data points configured as an
event.
The send buffer has a maximum size of 64000 events divided into equal parts for all
configured communications partners. The size of the frame memory can be set in STEP 7,
refer to the section SNMP (Page 42).
Messages / e-mail
Up to 10 messages can be configured in STEP 7 and sent as e-mails.
IPsec tunnel (VPN)
Up to 8 IPsec terminals can be established for secure communication with other security
modules.
Firewall rules
The maximum number of firewall rules in advanced firewall mode is limited to 256.
The firewall rules are divided up as follows:
Maximum 226 rules with individual addresses
Maximum 30 rules with address ranges or network addresses
(e.g. 140.90.120.1 - 140.90.120.20 or 140.90.120.0/16)
Maximum 128 rules with limitation of the transmission speed ("Bandwidth limitation")

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 and is the answer not in the manual?

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 Specifications

General IconGeneral
Compatible ControllersS7-1200
InterfaceEthernet
Power Supply24 V DC
Number of Possible Connections8
Mounting TypeDIN rail
Weight200 g
Data Transfer Rate10/100 Mbps
ProtocolsTCP/IP, UDP, DNP3, IEC 60870-5-104
Supply Voltage20.4 ... 28.8 V DC
Current Consumption100 mA
Operating Temperature-20 ... +60 °C

Related product manuals