EasyManua.ls Logo

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1 - Messages

Siemens SIMATIC NET TeleControl S7-1200 CP 1243-1
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
4.10 Messages
CP 1243-1
88 Operating Instructions, 12/2016, C79000-G8976-C365-02
Enable partner for inter-station communication
If the value of the data point is to be sent to an S7 station, select the option "Partner for inter-
station communication".
The telecontrol server and an S7 station cannot be selected as the partner for a data point at
the same time.
Partner number (inter-station communication)
Specify the partner CP for inter-station communication for the selected data point by
selecting the required partner from the drop-down list. The access ID of the relevant partner
is shown in brackets.
The partners you specified in the "Partner stations" > "Partner for inter-station
communication" can be selected.
Data point index
Index of the corresponding data point on the communications partner.
Note:
The data pair of the sending and receiving CP must have an identical data point index. A
receiving data point of CP 2 corresponds to a sending data point of CP 1 with the same
data point index.
For the opposite communications direction, a second pair of data points must be created:
A sending data point of CP 2 corresponds to the receiving data point of CP 1. Once
again, both have an identical data point index.
4.10
Messages
Configuring e-mails
If important events occur, the CP can send e-mails to a communications partner.
You configure the e-mail in STEP 7 in the editor for the data point and message
configuration. You can find this using the project tree:
Project > directory of the relevant station > Local modules > CP
For the view in STEP 7, refer to the section Configuring data points and messages
(Page 65).

Table of Contents

Related product manuals