Configuration
4.10 Messages
CP 1243-1
88 Operating Instructions, 12/2016, C79000-G8976-C365-02
Enable partner for inter-station communication
If the value of the data point is to be sent to an S7 station, select the option "Partner for inter-
station communication".
The telecontrol server and an S7 station cannot be selected as the partner for a data point at
the same time.
Partner number (inter-station communication)
Specify the partner CP for inter-station communication for the selected data point by
selecting the required partner from the drop-down list. The access ID of the relevant partner
is shown in brackets.
The partners you specified in the "Partner stations" > "Partner for inter-station
communication" can be selected.
Index of the corresponding data point on the communications partner.
● The data pair of the sending and receiving CP must have an identical data point index. A
receiving data point of CP 2 corresponds to a sending data point of CP 1 with the same
data point index.
● For the opposite communications direction, a second pair of data points must be created:
A sending data point of CP 2 corresponds to the receiving data point of CP 1. Once
again, both have an identical data point index.
Messages
Configuring e-mails
If important events occur, the CP can send e-mails to a communications partner.
You configure the e-mail in STEP 7 in the editor for the data point and message
configuration. You can find this using the project tree:
Project > directory of the relevant station > Local modules > CP
For the view in STEP 7, refer to the section Configuring data points and messages
(Page 65).